Technical Summary — At a Glance
| Specification |
Detail |
| Manufacturer |
ERI Corporation |
| Product Code |
BSP3240-T |
| Connection |
32 mm OD |
| Application |
HVAC / AHU condensate drainage |
| Pressure operation |
Positive & negative pressure |
| Dry pressure test |
Up to ±1500 Pa |
| Heater option |
24 V or 230 V |
| Typical Delivery |
3–5 working days |
Overview
The ERI BSP3240-T is a compact ball siphon designed for condensate drainage on AHU and HVAC systems. Its built-in ball valve helps maintain the drainage seal when condensate is absent, and the siphon is suitable for both positive and negative pressure applications.
The unit has a 32 mm OD connection and is designed for dry pressure tests up to ±1500 Pa. Optional 24 V and 230 V heater arrangements can be used where protection against freezing is required.
Specifications
| Specification |
Detail |
| Manufacturer |
ERI Corporation |
| Manufacturer / Product Code |
BSP3240-T |
| Product Type |
Ball Siphon / Condensate Drain Trap |
| Connection Size |
32 mm OD |
| Pressure Application |
Positive and Negative Pressure |
| Dry Pressure Test |
Up to ±1500 Pa |
| Heater Options |
24 V or 230 V |
| Fixing Bracket |
Supplied |
| Sealing Components |
Sealing cap and inner sealing ring supplied |
| Heater Cable Fixings |
Heater cable screws / retainer supplied |
| 40 mm Adaptors |
Two supplied |
Downloads
Technical Datasheet & Installation Instructions — PDF
Download PDF
Installation & Suitability
- Suitable for positive and negative pressure condensate drainage applications.
- Provide each HVAC condensate drain system with its own siphon.
- For positive-pressure operation, remove the bleed plug before use, as stated in the manufacturer instructions.
- Follow the manufacturer installation diagrams for correct pipe connection and drain orientation.
- The manufacturer marks horizontal outlet drain connection 2 as not recommended because water will be retained in the AHU.
View full manufacturer installation instructions — PDF
FAQs
Is the BSP3240-T suitable for positive and negative pressure systems?
Yes. The manufacturer information states that it is designed to operate under both positive and negative pressure conditions.
What size connection does the BSP3240-T have?
The main connection is 32 mm OD.
What pressure can the siphon handle?
The manufacturer information specifies dry pressure tests up to ±1500 Pa.
Can a heater be fitted?
Yes. Optional 24 V or 230 V heater arrangements can be added to help prevent freezing.
Are 40 mm adaptors supplied with the trap?
Yes. Two 40 mm adaptors are included with this product.